Skip to main content Skip to footer

Moisture-Related Problems: Identifying the Contributing Factors

May 15, 2023

WATER LEAKAGE WAS reported shortly after
substantial completion of a three-story, Class A
office building. The reported water leakage was
limited to the south elevation of the building
and occurred only on hot and sunny days that
were preceded by rainfall. The owner notified the
project team and asked them to resolve the issue
at hand. The glazing contractor performed hosewater
testing in accordance with AAMA 501.2,
Quality Assurance and Diagnostic Water Leakage
Field Check of Installed Storefronts, Curtain Walls
and Sloped Glazing Systems,1 which did not result
in any water leakage. The general contractor
did not offer another possible explanation. The
owner then asked a third party to investigate and
provide an objective technical opinion. Based
on an extensive forensic investigation, it was
determined that the reported water leakage was
the result of summertime condensation. This
conclusion was based on identifying a source of
water vapor, a driving force, and unobstructed
paths for the moisture-laden air to travel through
the building enclosure.
A notable aspect of this case study is
that other third-party experts appeared to
have misinterpreted the findings from the
investigation. One of them claimed that the
condensation was the result of a negative
building pressure, even though an independent
test report indicated the HVAC system was
operating at a positive pressure. Another expert
proposed a repair approach that would not have
properly contained the water vapor in the cavity
behind the brick veneer.
This article provides a relatable way to
evaluate the basic performance attributes
of building enclosure products and systems
by breaking down the technical concepts into
source, path, and pressure. Assigning these
items to an air- or water-leakage problem is
straightforward. The same concept can also be
applied to the flow of water vapor and heat, both
of which have an impact on condensation and
moisture accumulation.
This article is offered as a resource for forensic
engineers who perform failure analyses of
moisture-related building enclosure issues. It
also serves as a cautionary reminder to design
professionals that they should not arbitrarily
incorporate/locate components in a wall assembly.
BUILDING ENCLOSURE
PERFORMANCE ATTRIBUTES
AND PROBLEMS
Building enclosures are designed to protect inside
conditioned spaces from the outside environment.
That might sound like a straightforward
expectation, but there can be challenges in
achieving an even basic level of performance.
Every building has distinctive physical
features such as size, shape, and cladding
materials, just to name a few. Then there is
the geographic location, which dictates the
environmental conditions such as outside
temperature, wind, humidity, and rain. The
team of designers, contractors, suppliers,
and installers varies from project to project,
meaning each building is constructed by
different personnel. What could possibly go
wrong? This question is asked facetiously
because, unfortunately, building enclosure—
related problems occur all the time.
The most common construction defect claims
are moisture-related problems associated with
the building enclosure.2 These issues can be the
result of excessive air leakage, water leakage,
condensation, or moisture accumulation. In
some circumstances, a building will experience
multiple issues at the same time.
I have been hired numerous times as a
third party to provide an objective technical
evaluation for these enclosure-related issues,
and the forensic investigation usually reveals
a path for air or water leakage through the
building enclosure. Sometimes, there are
other contributing factors that might not have
manifested into a noticeable problem on their
own. Compared to an air- or water-leakage
problem, investigating the root cause of a
condensation or moisture accumulation problem
can be a bit more complicated, and guidance for
performing a failure analysis will be discussed
later in this article.
THE LEAK TRIANGLE
A simple concept for evaluating an air or water
leak through the building enclosure is the “leak
triangle,”3 which is composed of a source, path,
and pressure (Fig. 1). Removing any one of the

three parts of the triangle will resolve a leakage
issue. Therefore, as described in the following
sections, both product performance validation
for building enclosure components/systems and
forensic investigations of leakage problems involve
assessment of the leak triangle.
Air Performance Rating
Industry standards for determining the air
performance rating of various building enclosure
products and systems include ASTM E2178,
Standard Test Method for Determining Air Leakage
Rate and Calculation of Air Permeance of Building
Materials,4 and ASTM E283, Standard Test Method
for Determining Rate of Air Leakage through
Exterior Windows, Skylights, Curtain Walls, and
Doors under Specified Pressure Differences
across the Specimen.5 To perform these tests, a
static pressure differential is imposed across a
test chamber, which either “pulls” or “pushes”
air through the test specimen. The resulting air
leakage is measured in units of ft3/min (L/s). The
air leakage rate, which is determined by dividing
the amount of air leakage by the test specimen
area, can then be used to evaluate and compare
products. In terms of the leak triangle, the air is the
source, the test specimen comprises the path, and
the vacuum suction is the pressure (Fig. 2).
Air Leakage
There are unfavorable circumstances in which
excessive air leakage occurs through the building
enclosure. When such leakage happens,
the amount of water in the air (water vapor)
transported through the air (vapor transport)
will be much greater than if it would be diffused
through a material (vapor diffusion).6 Thus, air
leakage can be a significant contributing factor to
moisture-related problems.
Unobstructed paths such as unsealed joints
or holes will allow air to freely travel through
the building enclosure. Investigators can use
the test methodology described in ASTM E783,
Standard Test Method for Field Measurement of
Air Leakage through Installed Exterior Windows
and Doors,7 as a guide when looking to quantify
the amount of air leakage through the building
enclosure. Sometimes, the paths for air leakage
can be identified by visual observation. However,
temporary removal of cladding components to
create exploratory openings is required if the
deficient building conditions are concealed.
Revisiting the leak triangle, the earth’s
atmosphere is not a vacuum, and it would also be
unusual for wind pressure to exceed the product
performance rating for a sustained period of time.
Thus, the source and pressure components of the
Figure 1. The leak triangle.
Figure 2. Test apparatus for ASTM E283, Standard Test Method for Determining Rate of Air
Leakage through Exterior Windows, Skylights, Curtain Walls, and Doors under Specified Pressure
Differences across the Specimen.
Figure 3. Test apparatus for ASTM E331, Standard Test Method for Water Penetration of Exterior
Windows, Skylights, Doors, and Curtain Walls by Uniform Static Air Pressure Difference.
Test
Specimen
www.iibec.org IIBEC Interface • 21
leak triangle are generally not the primary focus
in an air leakage forensic investigation. Typically,
it is the path or paths that need to be addressed
to resolve an air leakage problem. Occasionally,
adjustments to the HVAC system may be needed
to help address a building pressure issue.
Water Performance Rating
A common test procedure for evaluating water
performance is defined in ASTM E331, Standard
Test Method for Water Penetration of Exterior
Windows, Skylights, Doors, and Curtain Walls
by Uniform Static Air Pressure Difference.8
Assigning the components of the leak triangle to
the procedure, the water is the source, the test
specimen is the path, and the vacuum suction
creates the pressure differential (Fig. 3). This
test standard specifies a constant water flow
for a certain amount of time. Upon completion
of the test, and assuming water leakage is not
observed, that product is then considered to be
“rated” for the tested static pressure differential.
Water Leakage
For water leakage to occur through the building
enclosure, there must be a source of water, a
path, and a pressure. ASTM E2128, Standard
Guide for Evaluating Water Leakage of Building
Walls,9 and AAMA 511, Voluntary Guideline for
Forensic Water Penetration Testing of Fenestration
Products,10 are industry-recognized guidance
for investigating water leakage through exterior
walls and window systems, respectively.
Similar to air leakage problems, waterleakage
problems typically involve a deficient
building condition that provides a path for
leakage through the enclosure. It is possible
that a negative building pressure is also a
contributing factor to the problem. On rare
occasions, an extreme horizontal wind-driven
rain event or flooding can exceed the capabilities
of a rated product or system.
Summarizing the Leak Triangle
Tables 1 and 2 provide side-by-side comparisons
of how the parts of the leak triangle apply to
product performance ratings and in-service
leakage problems. When evaluating the air
performance of a building enclosure product or
system, the key parameters are the air-leakage
rate in units of ft3/min/ft2 (L/s/m2) and the
static pressure differential in units of lb/ft2 (Pa).
Product performance ratings used to evaluate
water performance are described by the static
pressure differential in units of lb/ft2 (Pa).
When a building is experiencing an
air- or water-leakage problem, the forensic
engineer should investigate and analyze all
three components of the leak triangle. In my
experience, the failure analysis will generally
indicate a deficient building condition that
provided a path for the leakage to occur. Under
this scenario, addressing the path of leakage
would resolve the issue.
THE FLOW TRIANGLE
Using the same components as the leak
triangle (source, path, and pressure), the “flow
triangle” describes the flow of both water vapor
and heat. The flow triangle can be helpful when
analyzing moisture-related problems such
as condensation and moisture accumulation.
Before these issues are reviewed in further
detail, a brief overview of some building
enclosure components that control the flow of
water vapor and heat is warranted.
Vapor Permeance Rating
There are several ways to quantify water
vapor such as dew point temperature,
humidity ratio, water vapor partial pressure,
or water vapor concentration. When there
is a difference in the amount of water vapor
across the building enclosure, the water
in the air will travel from areas with higher
concentrations of water vapor to areas with
lower concentrations. For many geographic
Air Performance Rating Air Leakage
Assessment method Window system testing
per ASTM E283 Common failure analysis
Source Air leakage rate Air
Path Test specimen Holes, joints, interface conditions
Pressure Static pressure differential Wind (+/-), HVAC (+/-), stack effect (+/-)
Water Performance Rating Water Leakage
Assessment method Window system testing per
ASTM E331 Common failure analysis
Source Water spray rack Rain
Path Test specimen Holes, joints, interface conditions
Pressure Static pressure differential
Wind (+), HVAC (-), stack effect (-),
gravity, hydrostatic pressure, surface tension,
capillary suction
Table 1. Leak triangle comparison between air performance rating and air leakage
Table 2. Leak triangle comparison between water performance rating and water leakage
22 • IIBEC Interface February 2023
locations, the direction of water vapor travel is
typically from the outside to the inside of the
building in the summer and from the inside to
the outside in the winter.
One way to determine the rate of water vapor
transmission through a material is to perform
testing per ASTM E96, Standard Test Methods for
Water Vapor Transmission of Materials.11 There
are two different methods in this test standard
(wet cup and dry cup), the primary differences
being the amount of water vapor and direction
of the vapor flow (Fig. 4). With reference to the
components of the flow triangle, the water vapor
is the source (100% relative humidity [RH] for wet
cup and 50% RH for dry cup) in this test scenario;
the test specimen resists the flow of water vapor
along the path; and the differences in water
vapor provide the pressure (water vapor
partial pressure).
This testing provides a vapor permeance
rating in units of perms (ng/[Pa·s·m2]). When
comparing products, a lower vapor permeance
rating indicates that the product will provide
more resistance against the flow of water vapor.
Thermal Resistance Rating
Heat flows from hot areas to cold ones, and thermal
insulation can be used to minimize heat loss across
the building enclosure. A test for obtaining the
thermal performance of a material is ASTM C518,
Standard Test Method for Steady-State Thermal
Transmission Properties by Means of the Heat Flow
Meter Apparatus.12 This testing evaluates the thermal
resistance of a product, stated as the R-value. The
higher the R-value is, the more resistant the product
is to heat flow.
Applying the flow triangle model to the
test apparatus shown in Fig. 5, the hot plate is
considered the source of heat, the test specimen
resists the flow of heat along the path, and the
temperature differential is analogous to the
pressure component.
Condensation
Condensation occurs when the water in the air
changes from the gaseous phase to the liquid
phase. It will form when moisture-laden air
comes into contact with a material having a
surface temperature at (or below) the dew
point temperature. When a condensation
problem occurs, a rudimentary explanation
likely involves a high amount of water vapor or
a material surface that is too cold.
When performing a forensic
investigation, the first step is to identify the
source or sources of water vapor, and then
the path or paths for vapor transport should
be located. In cold climates, the forensic
engineer will also want to determine whether
materials with a low resistance to heat
flow (such as steel or aluminum) comprise
a continuous path through the building
enclosure, creating what is known as a
“thermal short circuit.”
Moisture Accumulation
Moisture accumulation develops when the
rate of wetting exceeds the rate of drying. In
many instances, moisture accumulation within
Vapor Permeance Rating Moisture Accumulation
Assessment method Vapor retarder component
testing per ASTM E96 Possible contributing factors
Source Water vapor Water leakage, air leakage, water
vapor, condensation
Path Test specimen
Location/placement and
permeance rating of a vapor
retarder
Pressure Water vapor partial pressure differential Water vapor partial pressure
differential
Thermal Resistance Rating Moisture Accumulation
Assessment method Thermal insulation component
testing per ASTM C518 Possible contributing factors
Source Hot plate n/a
Path Test specimen Location/placement and resistance
rating of thermal insulation
Pressure Temperature differential
(analogous comparison) n/a
Note: n/a = not applicable.
Table 3. Water vapor flow triangle comparison between vapor permeance rating and moisture accumulation
Table 4. Heat flow triangle comparison between thermal resistance rating and moisture accumulation
www.iibec.org IIBEC Interface • 23
Figure 4. Test apparatus for ASTM E96, Standard Test Methods for Water Vapor Transmission
of Materials.
Note: RH = relative humidity.
Figure 5. Test apparatus for ASTM C518, Standard Test Method for Steady-State Thermal
Transmission Properties by Means of the Heat Flow Meter Apparatus.
Publish
In
IIBEC Interface journal is seeking submissions for the following issues. Optimum article size
is 2000 to 3000 words, containing five to ten high-resolution graphics. Articles may serve
commercial interests but should not promote specific products. Articles on subjects that do not fit
any given theme may be submitted at any time.
The Technical Journal of the International Institute of Building Enclosure Consultants
December 2022 | Vol. XL No. 11 | $15.00
Technology
The Technical Journal of the International Institute of Building Enclosure Consultants
January 2023 | Vol XLI No. 1 | $15.00
The Building Enclosure
Submit articles or questions to Executive Editor Christian Hamaker at 800-828-1902 or chamaker@iibec.org.
ISSUE SUBJECT SUBMISSION DEADLINE
July 2023 Sub-Grade Waterproofing March 15, 2023
August 2023 Ethics April 15, 2023
September 2023 Trends in Roof and Wall Design May 15, 2023
October 2023 Coatings June 15, 2023
the building enclosure will accompany air- or
water- leakage problems. Thus, a failure
analysis for those potential problems should
be performed when commencing a forensic
investigation.
When analyzing a moisture accumulation
problem, the forensic engineer will also have
to consider the contribution of water vapor
and heat. Unlike an air- or water-leakage
problem, impeding the path component of the
flow triangle might not necessarily address a
moisture accumulation problem. This would
entail decreasing the permeance of the vapor
control layer or increasing resistance of the
thermal control layer, which under certain
conditions could inadvertently exacerbate the
issue.
As previously mentioned in this article,
there are industry guidelines that can be
referenced when investigating air- or waterleakage
issues. Dissecting and analyzing
the components of a moisture accumulation
problem, however, is not as straightforward.
After developing a hypothesis about the
potential components of the water vapor
and heat flow triangles, a thorough and
methodical investigation is necessary. It is
important to keep in mind that air or water
leakage, or both types of leakage, may be
contributing factors to the moisture problem.

Summarizing the Flow Triangle
Tables 3 and 4 summarize how the parts of the
flow triangle apply to the testing of building
components and the investigation of a moisture
accumulation problem. These tables can be used
as a reference but should not be considered a
comprehensive list of all possible contributing
factors.
The International Building Code13 has
classifications for materials that impede the
flow of water vapor (vapor retarders) as well as
restrictions, based on climate zone, for their
location/placement within a wall assembly. A
potential consequence of improper usage of a
vapor retarder is restricting the drying ability
of an assembly, which could be a contributing
factor to a moisture accumulation problem.
Incorporating a thermal control layer is an
important design consideration for the building
enclosure. The location/placement of thermal
insulation will influence both the water vapor
pressure profile and temperature gradient, both
of which have the potential to affect wetting and
drying rates. A hygrothermal analysis can serve
as a useful tool to analyze different building
enclosure assemblies and environmental
conditions. Alternatively, the American Society
of Heating, Refrigerating and Air-Conditioning
Engineers provides a rather simple, steady-state,
one-dimensional analysis called the dew-point
or Glaser method, accompanied with a couple
examples.14
SYSTEMS VERSUS
COMPONENTS
Pre-engineered building enclosure systems,
such as windows, typically have laboratorytested
air- and water-performance ratings.
Assuming that the system is properly installed
and coordinated with adjacent enclosure
systems, the rating provides a reliable
indication of in-service performance.
It should also be expected that the vaporand
thermal-control layers perform as indicated
on their respective product data sheets. When
these components are incorporated into an
exterior wall or roof assembly, they have an
impact on overall system performance, which
must be carefully reviewed and considered
during the design process. The use of a vapor
retarder requires additional scrutiny and
should not be arbitrarily integrated into the
building enclosure.15
TAKEAWAY
There is no shortage of complex topics to discuss
regarding today’s high-performance buildings
and their enclosures. Whether you are a design
professional or forensic engineer, a simple way
to evaluate the basic functional performance
attributes of these systems is to delineate and
analyze the components of the leak and flow
triangles (source, path, and pressure).
REFERENCES
1. Fenestration and Glazing Industry Alliance (FGIA).
2015. Quality Assurance and Diagnostic Water
Leakage Field Check of Installed Storefronts, Curtain
Walls and Sloped Glazing Systems. AAMA 501.2-15.
Schaumburg, IL: FGIA.
2. Grosskopf, K.R., P. Oppenheim, and T. Brennan.
2008. “Preventing Defect Claims in Hot, Humid
Climates.” ASHRAE Journal 50 (7): 40–52.
3. Edgar, J. 2012. “Air Barriers 101: Basic Theory
and Design.” In The Technology of Air Barriers: A
Durability and Design Collection, 1-7. Wharton, PA:
Technology Publishing Co..
4. ASTM International. 2021. Standard Test Method for
Determining Air Leakage Rate and Calculation of Air
Permeance of Building Materials. ASTM E2178-21A.
West Conshohocken, PA: ASTM International.
5. ASTM International. 2019. Standard Test Method for
Determining Rate of Air Leakage through Exterior
Windows, Skylights, Curtain Walls, and Doors under
Specified Pressure Differences across the Specimen.
ASTM E283/E283M-19. West Conshohocken, PA:
ASTM International.
6. Dalgleish, R., and L. Dalgleish. 2006. “The Dollars
and Common Sense of Air Barriers.” Interface
(January): 13–18. https://iibec.org/wp-content/
uploads/2016/04/2006-01-dalgleish.pdf.
7. ASTM International. 2018. Standard Test Method for
Field Measurement of Air Leakage through Installed
Exterior Windows and Doors. ASTM E783-02(2018).
West Conshohocken, PA: ASTM International.
8. ASTM International. 2016. Standard Test Method for
Water Penetration of Exterior Windows, Skylights,
Doors, and Curtain Walls by Uniform Static Air
Pressure Difference. ASTM E331-00(2016). West
Conshohocken, PA: ASTM International.
9. ASTM International. 2020. Standard Guide for
Evaluating Water Leakage of Building Walls.
ASTM E2128-20. West Conshohocken, PA: ASTM
International.
10. FGIA. 2008. Voluntary Guideline for Forensic Water
Penetration Testing of Fenestration Products. AAMA
511-08. Schaumburg, IL: FGIA.
11. ASTM International. 2016. Standard Test Methods
for Water Vapor Transmission of Materials. ASTM
E96/E96M-16. West Conshohocken, PA: ASTM
International.
12. ASTM International. 2021. Standard Test Method
for Steady-State Thermal Transmission Properties
by Means of the Heat Flow Meter Apparatus.
ASTM C518-21. West Conshohocken, PA: ASTM
International.
13. International Code Council. 2021. International
Building Code. Country Club Hills, IL: ICC.
14. American Society of Heating, Refrigerating
and Air-Conditioning Engineers (ASHRAE).
2017. “Vapor Point Pressure Profile (Glaser or
Dewpoint Analysis).” In 2017 ASHRAE Handbook—
Fundamentals, 27.8-27.10. Peachtree Corners, GA:
ASHRAE.
15. Lstiburek. J. 2011. “Understanding Vapor Barriers.”
Building Science Digests 106. https://www.buildingscience.
com/documents/digests/bsd-106-understanding-
vapor-barriers.