Skip to main content Skip to footer

Roof Design Considerations in Cold and High Altitude Regions

February 9, 2003

February 2003 Interface • 9
INTRODUCTION
The Rocky and Appalachian Mountains are areas that combine
cold winter weather and high altitudes. These regions are
not densely populated, so many roof designers are unaware of
the special design requirements for roofs within these areas. This
paper will address some of the key design elements that are typically
overlooked. It will include the following:
• These regions are prone to ice dam formation due to a
combination of building heat loss and solar radiation.
• Despite the perception of having dry climates, vapor
drive is still a problem, particularly when
ice dam protection membranes are
installed over the entire roof deck.
• Snow accumulation also requires that
snow retention on the roofs be
addressed.
• Roof ice melt systems are a critical
design component in helping to eliminate
ice dams.
• Roof drainage systems must be designed
with ice dam formation in mind.
A good roof design will address all of the
factors noted above.
ICE DAM FORMATION
Ice dam formation in cold and high altitude
regions is caused by building heat loss and solar
radiation.
Nature of Ice Dam Formation
Ice dams typically begin to form when the ambient air temperature
is 22°F and below. The ice dam begins to form at the
drip edge along the roof eave. Snow melt running down the roof
begins to accumulate behind the newly formed ice dam.
Eventually, the water overflows the initial ice dam, and in the
process, freezes over the lower level of ice. This increases the
thickness of the ice dam and increases the overhang of the ice
dam from the front face of the eave as shown in Figure 1. By this
process, ice dams can become very large and cause extensive
damage to the roof and building structure.
Figure 1: Typical ice dam formation at eave. Notice the eave is not even a substantial overhang.
10 • Interface February 2003
Ice Dam Formation Due to Building Heat Loss
Heat escaping through the roof can heat the snow to the
point that melting occurs. The resultant water from the snow
melt starts to drain off the roof. On sloped roofs, the water will
run toward the eave, which is typically colder than the remaining
portion of the roof. If sufficiently cooled before
draining off the roof, an ice dam will form along the eave. Overhanging
eaves are the most notorious for ice dam formations;
however, the roof eave need not be overhanging to be subject to
ice dams. In addition, roof valleys and lower roofs below upper
roofs can be prone to ice dam formation.
Contributing Problems
There are a number of factors that contribute to ice dam formation
due to building heat loss, including under-insulated roofs,
localized heat sources, exhaust stacks, inadequate roof ventilation,
and inadequate air barriers.
Under-insulated roofs allow excessive heat to rise through
the roof assembly, resulting in snow melt. A roof in these regions
should have a minimum thermal resistance value of R-38.
Recessed lighting within the ceiling is the most common “hot
spot” within attic and cathedral ceiling spaces. Exhaust stacks
release high temperature gasses that can melt substantial quantities
of snow. Chimneys of insufficient height and location on the
windward side of a roof will result in localized snow melt and ice
dam formation.
Inadequate roof venting is a major contributor to the formation
of ice dams and vapor drive problems, which will be
described below.
• Air movement within the attic or cathedral ceiling space
greatly aids in the removal of latent heat. Sufficient air
movement can even make up for other design or installation
deficiencies, most notably, vapor drive.
• Poor roof ventilation can also cause premature aging of
roof components, such as asphalt shingles.
• Inadequate roof ventilation is typical on roofs with complex
configurations, multiple roof valleys, and many
changes in plane. These configurations tend to reduce
soffit intake required for proper cross ventilation.
• Skylights, chimneys, roof curbs, and other roof penetrations
can restrict proper roof ventilation. Provisions for
redirection of cross-ventilating flow and addition of specialized
venting need to be made.
An inadequate air barrier is also a contributor to ice dams.
Air leaks through the air barrier can transport warm, moist air
that will help melt snow. In addition, air leaks may short-circuit
proper cross ventilation.
Resultant Problems
Ice dams create a
number of problems,
with the greatest
effects seen at roof
eaves and valleys as
exhibited in Figure 2.
Ice dams mechanically
damage the roofing,
flashings, and
roof drainage systems
(gutters and downspouts).
Melting ice
dams can create
water infiltration into
the building envelope,
damaging
building components
and interior finishes.
Ice weighs approximately
57 pounds per
cubic foot; it can
overstress the building
structure, particularly
gutters and
downspouts.
Attempts to mechanically
remove the ice dams may also result in damage to the roof
system.
Possible Solutions
A conventional roof system utilizing Uniform Building Code
venting minimum ratios of 1:150 or 1:300 (for cross ventilation)
typically do not have sufficient ventilation in these climates to
prevent ice dam formation due to building heat loss. In addition,
some code jurisdictions unwisely reduce the ventilation code
requirements. For example, Summit County in Colorado does
not require any roof ventilation because the climate is “dry.”
With the excessive use of ice dam protection membranes
installed over the entire deck, projects are developing severe
Figure 2: Severe ice dam formation along eaves and valleys.
February 2003 Interface • 11
problems with condensation due to vapor drive. Simply following
local code requirements does not guarantee the success of a
roof design.
Super-insulated roof systems have been designed to control
ice dam formation. A super-insulated roof system has insulation
with a minimum thermal resistance of R-45. While superinsulated
roofs help reduce ice dam formation due to building
heat loss, they do not address ice dam formation due to solar
radiation. As a general rule, super-insulated roofs are not ventilated.
While they typically include a vapor retarder, many have
roof decks that are entirely covered with impermeable ice dam
protection membranes such as “Ice and Water Shield.” With little
or no roof ventilation, these roof systems can have severe problems
with condensation due to vapor drive.
Cold roof systems are good for preventing ice dam formation
caused by building heat loss. Cold roof systems incorporate
increased roof ventilation beyond that required by code. They
include good roof insulation (R-38 minimum) and ventilate the
attic or cathedral ceiling space above the roof insulation. Cold
roofs keep the temperature of the roof deck and roofing systems
close to that of the exterior air temperature.
Cold roof systems may provide ventilation entirely under one
roof deck or two ventilation paths underneath an additional cold
roof deck installed over battens over the lower roof deck as
shown in Figure 3. For concrete and clay tile roof systems, the
second air passageway can be created by installing sleepers
underneath battens, which also improves drainage over the roof
underlayment. On complex roofs with many valleys, there may
be insufficient air intake at the soffit to provide adequate air
movement in areas of the cold roof. As a
result, heat tracing or another roof ice melt
system may be required in valleys. A cold
roof system will not address ice dam formation
due to solar radiation.
Roof ice melt systems can be used to
address ice dam formation not remedied by
the roof systems noted above. Roof ice melt
systems typically consist of heat tracing,
heated metal extrusions, or heated roofing
such as heated roof shingles. Roof ice melt
systems are typically required at roof eaves
and valleys. They should primarily be used
to address ice dam formation due to solar
radiation, not building heat loss.
Proper detailing and use of vapor
retarders and air barriers is beneficial in
eliminating ice dams. Typically, a vapor
retarder will be a good air barrier if properly
installed. The converse is not always
true. Vapor/air barriers are not typically
installed in a manner that meets theoretical
performance criteria. Unsealed laps,
mechanical attachment through the
vapor/air barrier and ceiling board, unsealed
penetrations, and improper tie-ins to the
wall vapor/air barrier greatly reduce the
effectiveness of these systems. Vapor/air
barriers should be well sealed to penetrations
with either tape or expanding foam.
The laps of the vapor/air barrier should be taped or sealed to
prevent air leakage or vapor transmission. In addition, the
vapor/air barrier should be tied into the wall vapor/air barrier.
ICE DAM FORMATION DUE TO SOLAR
RADIATION
Contributing Factors
Solar radiation melts snow in sunlit areas, and the resulting
water easily refreezes in shaded areas. Chimneys, gable roofs,
and other roof projections that create shadow lines are key areas
that promote ice dam formation due to solar radiation. Sunlight
can melt snow adjacent to these areas, and the resultant water
can easily refreeze once it enters a shaded area since the air at
high altitudes does not have sufficient insulating properties to
moderate the temperature extremes between sunlit and shaded
areas.
The north and east elevations of a roof are most prone to ice
dam formation due to solar radiation. Roofs oriented north and
south have the worst problems with these types of ice dams. To
reduce the likelihood of ice dams, roofs should be oriented east
and west to promote even heating and cooling of the snow.
Resultant Problems
The resultant problems are identical to those described in ice
dam formation due to building heat loss noted above.
Possible Solutions
The three different roof systems (conventional, super-insulat-
Figure 3: Example of cold roof configuration.
12 • Interface February 2003
ed, or cold roof) noted above will not remedy ice dam formation
due to solar radiation. Control of shadow lines, roof pitch, and
roof ice melt systems will help eliminate these types of ice dams.
Roof orientation relative to north should be considered carefully.
East and west facing roofs have fewer problems with ice
dams. In addition, the location and sizing of gable roofs, chimney
stacks, and other roof projections should be reviewed for
effect on shadow lines that may promote ice dams.
The roof pitch also affects ice dam formation due to solar
radiation. Steeper or shallow roof pitches can reduce the formation
of ice dams; however, other design considerations must be
evaluated before ultimately deciding on the roof pitch to be
used.
Roof ice melt systems are the most common method for
addressing ice dam formation due to solar radiation. The other
solutions noted above may not be feasible, requiring the use of
roof ice melt systems. While these systems are effective in reducing
ice dams, they
require electricity,
increasing energy
costs.
VAPOR DRIVE
A Summary of Vapor
Drive
In cold and high
altitude climates, outward
vapor drive is
greatest during the
winter heating season.
The warm air within
the interior holds
more moisture than
the cold air outside.
Moisture contained
within the air creates
a vapor pressure.
Accordingly, the
warm, moist air on the inside creates a higher vapor pressure
than the cold, dry air outside. While the relative humidity does
correlate to the amount of moisture within the air at a given
temperature, a direct comparison of relative humidities at different
temperatures does not immediately indicate which has the
most latent moisture. In other words, room-temperature air at 30
percent relative humidity has a higher vapor pressure than 20-
degree air at 80 percent relative humidity. The differences in
these vapor pressures results in a directional drive, whereby
moisture will migrate from areas of higher vapor pressure to
areas of lower vapor pressure.
Each building material has a unique resistance to moisture
vapor transmission. Building components with a resistance (or
Reps) of 1 or greater are considered vapor retarding materials.
Conversely, components with a resistance lower than 1 Rep are
considered vapor permeable materials. Choice of vapor retarder
must take into account the vapor resistance of the vapor retarder,
plus the resistance of all other building components within the
roof assembly. Other building components such as ice dam protection
membranes may have a very high resistance to vapor
drive, which may adversely affect the migration of moisture
within the roof assembly.
Contributing Factors
Inadequate or poorly installed vapor retarders are primary
factors that result in condensation within the roof assembly due
to vapor drive. A 4-mil polyethylene vapor retarder has a theoretical
resistance of 12.5 Reps; however, WR Grace “Ice and
Water Shield” has a resistance of approximately 200 Reps.
Furthermore, the polyethylene is much more likely not to perform
as expected due to the propensity for unsealed laps,
unsealed penetrations, and penetration by mechanical attachment
for the ceiling board. On the other hand, “Ice and Water
Shield” is well adhered and continuous, with sealed laps and selfsealing
properties around mechanical attachment penetrations.
The effect of this problem is shown in Figure 4.
Air leakage from the interior spaces into the attic or cathedral
ceiling space
can also be a major
contributor to
vapor drive problems.
Air movement
can transport
about 1000 times
more moisture than
vapor drive alone,
which transports
moisture by diffusion.
Ideally, the
vapor retarder will
also act as the air
barrier. Unsealed
penetrations and
lack of tying the
roof vapor
retarder/air barrier
into the wall vapor
retarder/air barrier
create localized air
leaks that can result in condensation.
Non-breathing underlayments and ice dam protection membrane
can promote condensation within the roof assembly. As
noted above, “Ice and Water Shield” and other similar selfadhered
ice dam protection membranes have outstanding resistance
to vapor drive. In most cases, this is not their intended
function, resulting in the greatest potential for condensation on
the building component directly underneath, which is typically
wood roof sheathing. This is not to imply that ice dam protection
membranes should not be used, but careful consideration of
their use and placement needs to be exercised. Simply specifying
their installation over the whole roof deck, assuming that the
result will be a roof bulletproof against leaks, will likely produce
an undesirable outcome.
Resultant Problems
The main result of vapor drive problems is condensation
within the roof assembly. The condensing water within and on
building components can lead to degradation and negatively
impact performance. Wood products are commonly used in roof
Figure 4: Example of condensation problem with installation of ice dam protection membrane and no
vapor retarder.
Ice & water membrane
February 2003 Interface • 13
framing and sheathing. For most species, if the percent moisture
within the wood exceeds 19 percent, wood decay will begin.
Excessive moisture levels within wood will also promote swelling
and warping, as well as mold and fungal growth that feeds on
the wood. Mold and fungal growth are also health concerns,
which the industry is beginning to take very seriously.
Roof condensation also damages most types of roof insulation.
Fiberglass batt insulation is commonly used in residential
building construction. When wetted, the fiberglass insulation
compresses, reducing the amount of air spaces that give the
product its insulating value. Consequently, the product’s thermal
resistance is reduced. Many times, this increases the condensing
rate, increasing the damage to building components.
Condensation due to vapor drive also leads to interior water
damage that is often misidentified as a “roof leak.” A contractor
may try many repairs that are ineffective at stopping these mysterious
“roof leaks.” The result is wasted time, money, and opportunity
for additional damages before the root cause is properly
identified.
Possible Solutions
All components within the roof assembly must be carefully
evaluated to prevent vapor drive problems. The vapor retarder/
air barrier must be properly specified and installed. The vapor
retarder should be installed on the warm side of the roof insulation.
Proper detailing and installation of these systems are also
required around penetrations and tie-ins to wall vapor retarders/
air barriers.
Adequate and controlled roof ventilation is very effective at
preventing condensation within the roof assembly. Cold roof
systems, as described above, provide good ventilation that minimizes
the risk for vapor drive problems.
The use of breathable roof underlayments should be considered.
Newer underlayments are available on the market that have
excellent resistance to hydrostatic pressure yet are very vapor
permeable. Their use on the field of the roof will greatly reduce
the potential for vapor drive problems.
SNOW RETENTION
Snow falls in a variety of densities and moisture
contents. Melting and refreezing “ripens” the
snow, creating different layers. These different
layers create shear planes that permit movement
of upper snow layers under the right circumstances.
Contributing Factors
Roof pitch has the greatest effect on snow
retention. Roof pitches of 4:12 to 9:12 typically
require retention devices to keep the snow in
place. Roof pitches in excess of 9:12 make snow
retention difficult or impossible.
Different roofing systems have varying kinds
of surfacing that affect snow retention. Metal
roof systems have a low coefficient of surface
friction that permit snow movement at lower
roof pitches. Asphalt shingle roofs are fairly
coarse and resist snow movement on steeper roof
pitches.
Inadequate retention devices promote snow movement. Snow
brackets (snow guards) are sometimes ineffective at roof slopes
7:12 and greater. The spacing of snow brackets is sometimes
inadequate. Snow fences may be required to resist snow movement
on steeper pitches.
Snow accumulation depth also affects its movement. Snow
brackets have limited heights and will not prevent movement
when accumulation significantly exceeds the height of the
device. Snow fences increase the accumulation depth that can be
retained on the roof.
Resultant Problems
Uncontrolled snow movement can damage the roofing, flashings,
and roof drainage systems. Clay and concrete tile can
break, and metal roofing can be damaged when snow falls onto
the surface. There is a risk of injury to people and damage to
lower building components and structures when snow slide is
not controlled.
Possible Solutions
Snow movement should be minimized to prevent injury to
people or damage to buildings. Snow slide can be controlled
with roof pitch and roof surfacing, but consideration should also
be made for proper roof drainage and roof ventilation when
choosing a particular roof slope. Roof slopes between 4:12 and
7:12 typically meet all of these requirements.
Snow bracket size and spacing should be carefully examined
to see if they will be sufficient to prevent most snow movement.
The structural attachment and penetration detailing through the
roof system need to be thoroughly reviewed. Snow fences retain
more snow than snow brackets, so attachment to the building
requires structural engineering. An example of a snow fence is
shown in Figure 5. Retention of snow increases the live load on
the roof structure. When retaining snow on the roof, it is imperative
to verify that the entire structure is designed to accommodate
the load.
Page 13
Quarter Page
B&W
Roof Hugger
Pick-up 1/03, page 10
Remove this border
14 • Interface February 2003
ROOF ICE MELT SYSTEMS
Types of Roof Ice Melt Systems
Stringing runs of heat tracing on the roof surface is the most
prevalent type of roof ice melt system, and it is the least expensive
to install. Heat cable degrades with exposure to the elements
and may not alleviate all ice dam problems. Heat tracing
also can be easily torn off the roof. Heat cable must have sufficient
wattage (10 watts per lineal foot minimum) to help prevent
ice dam formation.
Heated metal systems best address most of the issues associated
with ice dam prevention. They are typically the most effective
and aesthetic means of controlling ice dams; however, their
initial installation costs are significantly higher.
Heated asphalt roof shingles are relatively new on the market
and may become an effective method for prevention of ice
damming.
Design Considerations
The orientation of the building and shaded areas need to be
reviewed. Ice melt systems should be installed in areas prone to
ice dam formation due to solar radiation.
Even cold roof systems may not provide sufficient roof ventilation
within valleys to prevent ice dam formation due to building
heat loss. Running an ice melt system two-third the length of
the valley is typically sufficient to prevent the formation of ice
dams.
Heat tracing is typically installed in a zig-zag pattern on the
surface of the roof along eaves and valleys. This can be aesthetically
unappealing when snow is not on the roof. It also causes
snow on the roof to melt in an irregular pattern. Heated metal
systems are typically the most aesthetically appealing, but heated
roof shingles may also be an option.
ROOF DRAINAGE
SYSTEMS
Low-slope Roofing
Generally, internal
drains that benefit from
heating by the interior
spaces do not require ice
melt systems or special
consideration. External
drains and scuppers are
prone to ice formation,
which can prevent proper
roof drainage. Heating or
heat tracing may be
required.
Steep-slope Roofing
Exposed gutters are
typically at ambient air
temperature and are very
prone to icing. Ice weighs
approximately 57 pounds
per cubic foot and can
easily accumulate to the
point that gutters and
downspouts are ripped
from the roof. Heat tracing and adequate attachment to the
structure are required for external gutters on steep-sloped roofs.
Concealed gutters suffer less potential for structural failure
due to ice dam formation; however, use of heat tracing or underpan
heating is highly recommended.
CLOSING
Super-insulated roofs are not recommended for addressing
ice dam formation due to building heat loss, and conventionally
vented roofs may also be inadequate. The cold roof system provides
the greatest amount of ventilation to help prevent ice dam
formation due to building heat loss.
Roof ice melt systems are required at high altitudes to
address ice dam formation due to solar radiation. Roof orientation
and configuration can also help reduce the potential for ice
dams.
Proper selection of a vapor retarder considers all components
within the roof assembly. The vapor retarder requires careful
installation and tie-in to adjacent penetrations and the wall
vapor/air barrier. Proper roof ventilation will also help alleviate
problems associated with vapor drive.
Roof pitch and roofing types are key factors that affect the
requirements for snow retention devices. Snow brackets or snow
fences should be installed when required to keep snow from sliding.
The attachment and flashing details are important, as well as
ensuring the entire building structure is designed to retain anticipated
snow loads.
In cold and high altitude regions, some form of roof ice melt
system is almost always required. Heat tracing has the lowest initial
cost but may not have the performance, reliability, and aesthetics
required for the project. Heated metal systems have
many benefits but are significantly more expensive to install.
Figure 5: Snow fence and reinforcing cable system to retain snow on a 14:12 pitch roof.
February 2003 Interface • 15
Most roof drainage systems, with the
exception of internal drains, require heat tracing
to prevent ice formation that inhibits proper
drainage or that results in damage to the
roof drainage system.
Roofs in cold and high altitude climates
have design considerations not common in
most areas. In addition to the many concerns
always associated with roof construction, the
prudent designer will address ice dam formation
due to building heat loss and solar radiation,
vapor drive, snow retention, roof ice melt
systems, and roof drainage systems. A proper
roof design will balance all of these design constraints,
resulting in a roof system that will provide
long term performance. 
Steve Bunn is the head of Architectural Engineering
at Gillans, Incorporated in Westminster, Colorado. He
obtained a Bachelor’s Degree in Aeronautical
Engineering from the University of Washington in
1994. Bunn has eight years experience as an exterior
envelope consultant. He began his career working
with Colin Murphy at Exterior Research & Design,
where he ultimately headed the design division. Steve
joined Gillans in February 2000, and became head of
the exterior building systems department. He has
worked many fields within roof consulting, including
forensic investigation, laboratory analysis, code
approvals, design, and contract administration.
ABOUT THE AUTHOR
STEVE BUNN
A web-based British roofing consultancy information site has signed up
400 members since being launched 15 months ago. The site, www.roofconsult.
co.uk was founded by David Roy to help anyone involved in the design,
specification, or construction of roofs. Membership is free. The site covers a
range of issues, including British standards, technical updates, and legislative
changes. A recent addition is a U-value calculator for twin skin metal sheeting
utilizing the Ashgrid system.
LIKE TO SEE A PICTURE OF YOUR COMPANY’S PROJECT
GRACING THE COVER OF INTERFACE?
GIVE YOUR COMPANY INDUSTRY
EXPOSURE!
WE ARE LOOKING FOR ATTRACTIVE,
FOUR-COLOR, VERTICALLY-ORIENTED SHOTS.
Submit as original photograph or digital file (300 dpi, 8.5×11) to:
Kris Ammerman, RCI, 1500 Sunday Dr., Suite 204, Raleigh, NC 27607
E-Mail: krisamm@aol.com • Phone: 800-828-1902
LOOKING FOR A
FEW GOOD PICTURES
BRITISH WEBSITE AIDS
ROOF CONSULTANTS