Skip to main content Skip to footer

Roof Uplift Testing: Review of Applicable Standards and Industry Practice

March 23, 2017

3 2 n d RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 1 6 – 2 1 , 2 0 1 7 A b e n d r o t h a n d Mc E lv o g u e • 1 9 1
Roof Uplift Testing: Review of Applicable
Standards and Industry Practice
Jerry L. Abendroth, RRC, RWC, REWC, RBEC, RRO, CDT
Building Exterior Solutions, a Terracon Company
6975 Portwest Dr., Suite 100, Houston, TX 77024
Phone: 713-467-9840 • Fax: 713-467-9845 • E-mail: jabendroth@besgrp.com
and
Matthew R. McElvogue, RWC, RRO, PE
Building Exterior Solutions, a Terracon Company
3709 Promontory Pt., Suite 206, Austin, TX 78744
Phone: 512-827-3332 • Fax: 281-923-9588 • E-mail: mmcelvogue@besgrp.com
Abstract
Factory Mutual (FM) Global Insurance Company recommends that field uplift testing be
conducted for most adhered roofing systems in the hurricane-prone regions of the United
States and the Caribbean. Although this test procedure simulates the laboratory test, there
is much controversy regarding the use of the test in the field and the variables that can
affect test results. This presentation will explore the consultant’s role in the selection of
uplift testing protocols and testing procedures and help prepare participants to address the
types of problems that can be encountered during the specification and field practices of
roof uplift testing.
Speakers
Jerry Abendroth, RBEC, RRO, CDT, and Matthew R. McElvogue, RWC, RRO, PE – Building Exterior
Solutions, a Terracon Company, Houston, TX
Jerry Abendroth and Matthew McElvogue have performed ASTM and Factory
Mutual wind uplift testing on various projects for the past ten years. This testing has included
negative chamber testing and bonded uplift testing. During this same period, both men
have conducted forensic investigations of hurricane-related roof damage throughout the Gulf
Coast region. They have performed successful remediation designs of affected roof systems,
including supplemental attachment of roof systems that did not meet the design standards.
1 9 2 • A b e n d r o t h a n d Mc E lv o g u e 3 2 n d RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 1 6 – 2 1 , 2 0 1 7
PURPOSE AND SCOPE
FM Global (FMG) recommends in its
Property Loss Prevention Data Sheet 1-52
(Field Verification of Roof Wind Uplift
Resistance) that field uplift testing or fulltime
roofing construction observation be
conducted for most adhered roofing systems
in the hurricane-prone regions of the
United States and the Caribbean and locations
where design wind speeds are equal
to or greater than 100 mph. Although this
test procedure is intended to simulate the
laboratory test, there is much controversy
regarding the use of the test in the field and
the variables that can affect test results.
The following sections will explore the
consultant’s role in the selection of uplift
testing protocols and testing procedures
and will help prepare the reader to address
the types of problems that can be encountered
during the specification and field
practices of roof uplift testing. Topics that
will be addressed include applicable FMG
and ASTM testing standards and common
errors and challenges in specification and
testing. Additionally, several case studies
will be presented, as well as lessons
learned, including successful and problematic
roof uplift testing projects. Topics from
these case studies include a selection of
field uplift test pressures, and number and
locations of uplift testing.
Tests Summary
FM Loss Prevention Data Sheet 1-52
provides for two methods of testing wind
uplift resistance: the negative pressure
test and the bonded pull test. The negative
pressure test utilizes a 5-ft. x 5-ft. dome
that is placed on the roofing membrane.
Air is then pumped from the dome to
create negative pressure (suction) to the
roof membrane at an initial pressure of
15 pounds per square foot (psf); then the
negative pressure is increased in increments
of 7.5 psf, with each increment held
for one minute. This process is continued
until the design test pressure multiplied
by a factor of safety (1.25 for the current
version of the standard, 1.5 for previous
versions) is reached within the dome or
until failure occurs. A bar with a deflection
gauge is positioned in the center of
the chamber to measure deflection of the
roof membrane. Because the test was
initially performed using a durable skylight
dome, this test process is sometimes
referred to as the “bubble test.” In recent
years, test pressures have been increased
substantially, requiring the use of negative
pressure domes constructed of stronger
materials.
A parallel test standard is the American
Society for Testing and Material’s (ASTM’s)
E907, Standard Test Method for Field Testing
Uplift Resistance of Adhered Membrane
Roofing Systems. The two tests are similar
in that they use the same test apparatus
and load application/cycling; however,
there are some significant differences. With
regard to chamber placement, FMG recommends
that the chamber be placed “between
roof supporting beams or joists (where practical).
The exception is when testing roofs
on pre-cast concrete roof decks, the test
is to be located over the joints in the precast
concrete deck.” ASTM E907 does not
include provisions or recommendations for
placement relative to framing or joints, but
does indicate that roof surface stiffness may
be influenced by the roof deck and framing
stiffness. In 2012, the ASTM E907 standard
was withdrawn because it had not been
updated as required by ASTM.
Another notable difference between the
FMG and ASTM uplift tests is that the
FMG 1-52 test requirements for allowable
deflection are often more restrictive than
ASTM E907. When using FMG 1-52 to test
adhered membranes on wide rib steel deck,
the maximum allowable roof surface deflections
are ¼ in. for pressures up to 60 psf,
½ in. for pressures between 60 psf and 120
psf, and ¾ in. for pressures between 120
psf and 180 psf. The standard allows higher
deflections for systems with intermediate or
narrow-rib roof deck and for adhered roofing
systems with mechanically attached
insulation or thin cover boards. According
to ASTM E907, up to 1 in. deflection is
allowable at any test pressure.
FMG 1-52 also provides a procedure for
testing the roof system by bonding to the
membrane surface and lifting to simulate
negative pressure. The bonded uplift test
utilizes two 2-ft. x 2-ft. pieces of plywood,
which are fastened together to provide a
stiff lifting platform for the roof membrane.
The plywood is then adhered to the smooth
roof surface with steep asphalt, cold adhesive,
or another bonding material that is
compatible with the roof system. After an
appropriate curing period, the roof system
is cut at the perimeter of the plywood. The
attached plywood/roof assembly is then
attached to a scale/tripod assembly, and
upward force is applied in increments of
7.5 psf starting at 15 psf and held for one
minute at each increment until 1.25 times
the design pressure (or failure) is obtained.
Probably the most significant difference
between the standards is that FMG 1-52 is
accepted by FMG for field-testing of roofing
assemblies for buildings insured by FMG,
where ASTM E907 is not.
ROOF UPLIFT DESIGN
Bernoulli Principle
In short, Bernoulli’s Principle states
that an increase in the velocity of a fluid
(air, in the case of wind design) over an
object is accompanied by a decrease in the
surface pressure applied to that object.
This basic principle has a wide range of
applications throughout numerous industries,
including piping systems, aeronautical
design, and building enclosures. When
the Bernoulli equation is applied to calculate
pressure differentials between the
roof system and the wind flow above it, the
equation is narrowed down to the following
equation, where ρ is the density of the fluid
(air in this case) and 𝑣 is the velocity (speed)
of the fluid.
Table 2 in FMG 1-52, “Passing Uplift
Test Pressures for Enclosed Low-Slope
Buildings,” lists critical test pressures associated
with FMG roof wind ratings. This table
provides negative pressure criteria for three
sections of the roof (field, perimeter, corner).
Roof Uplift Testing: Review of Applicable
Standards and Industry Practice
3 2 n d RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 1 6 – 2 1 , 2 0 1 7 A b e n d r o t h a n d Mc E lv o g u e • 1 9 3
These values are fundamentally developed
from the parameters noted in Chapters 26
through 30 of the American Society of Civil
Engineers (ASCE)/Structural Engineering
Institute (SEI) Standard 7-10, Minimum
Design Loads For Buildings and Other
Structures. The ASCE 7-10 wind velocity
pressure calculation has numerical multipliers
KZ, Kzt, and Kd to account for
the types of situations in which the equation
may be applied. Earlier versions of
the above-noted standard also included an
importance factor “I,” which was eliminated
in the 2010 version through development of
additional wind speed figures. The equation
is below:
As can be seen above, the velocity
pressure equation in the ASCE 7 manual
is derived from Bernoulli’s Principle.
Although this principle is used for various
applications, it does have its limitations
and restrictions. Therefore, various
modifications and factors are employed to
apply Bernoulli’s basic principle to specific
applications. In our world of roofing, the
terrain, building height, safety factors, and
air densities must all be accounted for in
order to determine acceptable and sound
pressures from which uplift wind ratings
can be determined.
The FMG 1-52 test is intended to simulate
the pressures derived from these equations
applied to the roofing system. A pressure
differential equal to what has been
previously calculated and/or determined
through methods in accordance with ASCE
7 or identified through FMG 1-52 (and associated
standards) is created through the
use of a vacuum. The pressure is held for a
minute (Section 2.1.1.8 of FMG 1-52 2012),
and if the roof holds per the parameters set
forth in FMG 1-52 (discussed elsewhere),
the specimen is deemed a pass.
FMG 1-52 FIELD VERFICATION OF
ROOF UPLIFT RESISTANCE
FMG 1-52 Changes From February 2007
to April 2009 Standards
The version of FMG 1-52 issued in April
of 2009 includes several significant changes
from the previous version. The most significant
change was that the test was not
recommended for new roof systems that
are mechanically attached to certain roof
deck types. These roof deck types are steel
(minimum 22 gauge), wood, cementitious
wood fiber plank, and structural concrete
(minimum 2500 psi).
Another modification provided in the
April 2009 FMG 1-52 was to increase the
allowable deflection for metal decks. For
wide rib steel decks where the test pressure
exceeded 60 psf, FMG allowed an additional
¼-in. deflection for each 60 psf increment
of testing. If an intermediate or narrow rib
deck was used, FMG allowed the deflection
to be twice the previous limit up to a maximum
of 1 in. deflection.
In addition, FMG recommended that
all rooftop observers who were not directly
involved with the test equipment should not
stand directly adjacent to the test area during
testing. Other changes to the standard
included guidance for those conducting
testing on how to interpret the results.
FMG 1-52 Changes From April 2009 to
July 2012 Standards
One major theme in the changes from
the 2009 to the 2012 standard is the
distinction between “testing” and “field
testing.” This clear distinction is apparent
in some of the items changed/added in
the specification. First and foremost, the
name of the standard has been revised
to “Field Verification of Roof Wind Uplift
Resistance” from the previous title of “Field
Uplift Tests.”
Along with other modifications, FMG
has added a whole new method to predict
wind uplift performance of an approved
roof system (Roofnav assembly number,
FMG Approval Report, etc.) without having
to test the system itself. This method,
“Visual Construction Observation,” or VCO
for short, is stipulated under section 3.5 of
the 2012 FMG 1-52 standard. Under this
provision, a third-party observer (VCO)
must be present “full-time” during the
installation of the roof system, and through
daily report documentation and structured
observation, the roof system may forgo wind
uplift testing (bonded or negative uplift).
Additionally, the standard specifies that the
construction observer (CO) must not be a
direct employee of the owner, design professional,
or installing roof contractor to avoid
potential conflicts of interest. The third-party
CO is to verify the correct materials are
being utilized, verify construction practices
are in compliance with project documents,
note any deficiencies in workmanship, and
verify that all corrective measures are
implemented per FMG and project document
requirements.
Another modification involves test method
recommendations. Previously, a statement
existed in paragraph 2.1.1.3 of the
2009 FMG 1-52 that the bonded uplift test
was not recommended where any type of
mechanically fastened cover or insulation
was used. However, in the 2012 FMG 1-52,
Table 1, “Recommended Tests for Various
Roof Systems,” was added, and this table
lists the applicability of the two test methods
for various roofing types. See Table 1.
1 9 4 • A b e n d r o t h a n d Mc E lv o g u e 3 2 n d RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 1 6 – 2 1 , 2 0 1 7
Table 1 – FMG 1-52 Table 1, Recommended Tests for Various Roof Systems.
MF SP, MF FA SP,
BUR2, or MF MF Sp1, MF BUR, FA BUR
Type of Test or ModBit2 to BUR2, or or ModBit or ModBit FA SP Metal Ballasted
Analysis/Roof Type Deck Other ModBit2 to w/MF w/FA w/FA Roofs (See DS 1-29)
than LWIC LWIC Insulation Insulation Insulation
Negative Pressure Test DNA R1 R R R DNA DNA
Bonded Uplift Test DNA NR NR R R DNA DNA
1. Fastener spacing does not exceed 2 ft. (0.6 m) in both directions.
2. Base sheet is mechanically attached, and upper plies are adhered.
MF – Mechanically fastened R – recommended FA – Fully adhered NR – Not recommended
SP – Single-ply membrane BUR – Built-up roof ModBit – modified bitumen DNA – Does not apply
Metal Roofs – Standing seam (concealed clip securement) or lap seam (through-fastened)
Another modification involves the number
of bonded uplift tests required. In conformance
with the FMG 1-52 standard, a
bonded uplift test utilizes a sample that is
substantially smaller than that of the negative
pressure test (4 sq. ft. instead of 25 sq.
ft.). The 2012 FMG 1-52, paragraph 2.1.3.4,
states, “Conduct four times as many bonded
uplift tests (BPT) as recommended by Table
3, Figure 1 and Recommendation 2.1.9 to
account for the smaller test sample area
than that recommended for the negative
pressure test (NPT). The four BPT samples
should be prepared in close proximity to
each other, taking into consideration that a
complete cut needs to be made down to the
top of the deck around the entire perimeter
of the sample, and that bearing points are
required for the tripod legs. This allows
testing of the same approximate sample
area as in the NPT, and minimizes the
area requiring repair after.” Although this
paragraph states “…in close proximity to
each other,” FMG does not clearly indicate
how far away samples must be tested. The
above-referenced Table 3 is shown here in
Table 2.
Revisions also include calculation of
the required pressure for the uplift tests
(bonded or negative). Previously, paragraph
2.1.1.8 of the standard indicated the use of a
safety factor of 1.5 with the design pressure
to achieve the “passing uplift test pressure.”
The 2012 FMG 1-52, paragraph 2.1.1.8, now
specifies a factor of safety of 1.25.
Some additional failure criteria have
also been addressed in section 2.1.2.7. If
the cover board is observed to crease below
design pressure (factor of safety of 1.0), it is
indicative of a failure with the cover board
(crack formation). The standard also has
provided some illustrative examples (photographs)
in the new 2012 standard.
Examples of Field Uplift Testing Vs.
Actual Performance
Following Hurricanes Katrina (2005)
and Ike (2008), several testing agencies
used wind uplift testing to determine the
viability of existing roof systems. The author
observed one test conducted on a 25- to
30-year-old roof system that had been
mopped directly to lightweight insulating
concrete. The roof system had withstood the
hurricane with little gravel ballast displacement
(scour) and little water penetration
into the building; however, it could not pass
the FMG 1-52 test. Therefore, while it did
not meet the FMG 1-52 deflection criteria, it
was able to survive a major hurricane with
minimal damage to the roofing system.
In another example, a 25-year-old
built-up roof system that had a partial
blow-off during a hurricane event was
tested to a FMG 1-90 Wind Rating. The
roof consisted of a three-ply built-up system
over tapered perlite insulation. All
layers had been mopped in steep asphalt.
The remaining sections of the roof system
passed the FMG 1-52 test, even after adjacent
sections of the roofing system had
blown off during the hurricane. In this
case, although the roof system passed the
field uplift tests, large roof areas failed
during a hurricane.
NRCA Articles
It is important to consider input from all
sources when evaluating testing procedures
and protocols. For this reason, organizations
such as ASTM utilize committees for
development and maintenance of test standards.
These committees generally consist
of a broad range of members, including
manufacturers, contractors, design professionals,
and subject matter experts. The
National Roofing Contractors Association
(NRCA) is the largest membership organization
for roofing contractors. This organization
provides valuable feedback to a wide
variety of concerns as they affect the roofing
industry (safety, building codes, product
usage, and testing, just to name a few).
In December 2008, the NRCA published
an article in its Professional Roofing magazine
entitled “Experiences With FMG Global
Guidelines: Concerns Regarding FM Global
Field Uplift Testing Guidelines Persist.” In
the article, Associate Executive Director
of Technical Services Mark Graham listed
the results of a survey conducted by NRCA
regarding FMG 1-52 testing. The scope of
the survey is listed below:
“NRCA received reports for more than
8,000 roofing projects. Compliance with
FM Global guidelines was reported to be
specified in about 26 percent of those
projects. FM Global was reported to be the
property insurer in about 3 percent of those
projects.”
The following feedback was received:
• Roof systems passed the field uplift
tests only about 55 percent of the
time.
• Sometimes reports were issued that
did not provide proper information
about the pass or failure of the roof
system.
• Several respondents stated that
“FM Global required field uplift
tests to be conducted on existing
roof systems (including one that
has been in place for more than 23
years), apparently as a condition
of FM Global’s insurance renewal
process.”
Graham concluded this section of the
article with the following statement:
Although the survey results are
not statistically representative [n]or
significant of the overall U.S. roofing
industry, the information provides
a clear basis for roofing professionals’
continuing concerns with FMG
Global guidelines.
Graham concludes the article thus:
Given the results of NRCA’s survey,
clearly it is time for FM Global
to re-evaluate its reliance on field
uplift testing as a post-construction,
quality-assurance measure.
NRCA maintains—as it has for
years—the most effective means of
ensuring the quality of low-slope
roof system application is by the
continuous visual monitoring of the
application process at the time of
roof system installation.
In a follow-up article issued in July
2009, Graham evaluates recent changes
to the FM 1-52 test and adds the following
remarks concerning NRCA’s position
regarding testing.
3 2 n d RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 1 6 – 2 1 , 2 0 1 7 A b e n d r o t h a n d Mc E lv o g u e • 1 9 5
Table 2 – FMG Table 3, Minimum Number of Negative Pressure Tests.
Roof Area (A, ft2, or m2) Minimum No. of Tests
A ≤ 10,000 (1,000) 3 (1 F, 1 P, 1 C)
10,000 (1,000) ≤ A ≤ 60,000 (6,000) 5 ( 2 F, 2 P, 1 C)
A > 60,000 (6,000) or multiple adjoining roof areas See Section 2.1.1.9 and Figure 1
F = Field of roof P = Perimeter of roof C = Corner of roof
NRCA continues to strongly oppose
field uplift testing, such as FM 1-52,
as a measure of quality assurance
for low-slope roof system application.
The test method’s variability
and lack of repeatability and operator
sensitivity, as well as lack of
correlation between such test data
and FM Global’s laboratory-derived
approval classifications, make data
and results from FMG 1-52 testing
noncredible.
Some of FM 1-52’s latest revisions
indicate FM Global is beginning to
recognize roof deck deflection’s influence
on FMG 1-52’s test results.
Because a roof deck’s design, installation
and deflection are not controlled
by the roof system applicator,
this further indicates FMG 1-52 is
not appropriate as a roof application
quality assurance measure.
Also, FM Global’s recommendation
that there be no movement near
the test apparatus between the time
the deflection gauge is zeroed out
and when the test is complete is
not feasible with some of the equipment
and procedures used during
the tests.
NRCA maintains—as it has for
years—the most effective way to
ensure the quality of a low-slope
roof system application is continuous
visual monitoring of the application
process during roof system
installation.
We certainly would agree that a sound
quality assurance program with aggressive
field quality control is the best method to
limit potential deficiencies in the installed
roof system that can lead to catastrophic
failures during high-wind events. In fact,
FMG has included verbiage to recognize
full-time monitoring of roof installation
in lieu of field testing. However, monies
for continuous monitoring of roof system
installation are rarely allocated with project
budgets or set aside by building owners.
Owners typically make statements such as
professional general contractors and subcontractors
are hired to install the work per
the contract documents, and the owners
should not have to expend additional monies
to ensure that the job is done right.
The following section includes five case
studies that include field uplift testing as
an evaluation measure, construction compliance
quality control measure, or both.
Following the case studies, conclusions
regarding the authors’ opinions related to
the use of field uplift testing are presented.
CASE STUDIES
Case Study 1
Building Type: Hotel/Hospitality
Location: West Texas
Roof Age: 1-2 years
Roof Deck: Metal deck
Roof Construction: Multiple layers of polyisocyanurate
insulation
¼ in. glass-mat, waterresistant,
gypsum
cover board
60-mil EPDM fully
adhered roof system
Roof Height: 165 feet
Roof Uplift Pressures (Design):
Field 41.64
Perimeter 65.35
Corner 89.60
During the spring of 2012, the Lubbock,
TX, area experienced a high-wind event
that was typical for the area. Regional
weather reporting stations recorded maximum
wind gusts of 63 miles per hour
over several hours during daylight hours.
During the wind event, the southwest corner
of roof system ballooned, causing a substantial
portion of the roof to be dislodged
and damaged.
The roof manufacturer was contacted to
repair the roof system under the terms of
the warranty. The warranty issued by the
manufacturer included language that listed
55 mph as the maximum “warranted” wind
speed for the roof system. The roof manufacturer
denied the repair claim.
The insurance company for the hotel
hired several engineering firms to investigate
the mode (or modes) of failure of the
roof system. After removing the temporary
EPDM membrane over the damaged area,
the engineers and consultants observed the
elements of the damaged roof system. These
observations provided a basis for discussion
and conclusions. After visual observations,
FMG 1-52 testing was performed at six locations.
Results are shown in Table 3.
Findings and Testing Applicability
Test cuts were made at all test locations.
At each location, delamination was
observed within the gypsum cover board;
and at all locations, the delamination
extended beyond the test cut. Delamination
was observed immediately below the cover
board top facer, within the matrix of the
cover board gypsum core, and immediately
above the cover board bottom facer.
No delamination was observed between the
EPDM sheet and the cover board top facer,
between the cover board bottom facer and
the insulation, between layers of insulation,
or between the insulation and the concrete
deck. As the field tests showed that many
locations failed at approximately half of
design pressures, and the failure occurred
within the plane of the cover board, it was
determined that a material failure, not an
installation failure, was responsible for the
partial roof failure.
In this case, the consistent failure of
the roof system, often at or near half of the
design values, along with visual confirmation
of the failure mode, accurately reflected
the cause of the roof failure and the fact
that the roof system was never capable of
withstanding design wind loads. Therefore,
roof uplift testing provided a reliable predictor
of roof performance.
1 9 6 • A b e n d r o t h a n d Mc E lv o g u e 3 2 n d RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 1 6 – 2 1 , 2 0 1 7
Table 3 – Test results summary.
Test Number Test Deflection Comments
Pressure (inches)
(psf)
Test 1 (Corner) 37.5 0.26*
Test 2 (Corner) 45.0 Ballooned Failed 29 seconds into test cycle
Test 3 (Perimeter) 30.0 0.33*
Test 4 (Perimeter) 37.5 Ballooned Failed 14 seconds into test cycle
Test 5 (Corner) 52.5 Ballooned Failed 21 seconds into test cycle
Test 6 (Field) 37.5 Ballooned Failed 20 seconds into test cycle
* = Exceeds allowable deflection
Case Study 2
Building Type: Hospital/Medical Center
Location: Mobile, Alabama
Roof Age: 25-30 years
Roof Deck: 1-in. corrugated metal
pan deck
Roof Construction: Lightweight insulating
concrete
Coal tar pitch roof with
aggregate
Roof Height: 20 ft.
Roof Uplift Pressures: Not available
On August 29, 2005, Hurricane Katrina
struck the Gulf Coast of the United States.
The storm made landfall as a Category 3 rating
on the Saffir-Simpson Hurricane Scale.
According to the National Weather Service,
the storm brought sustained winds up to
150 miles per hour and stretched some 400
miles across. Because of the power of the
storm, widespread damage and flooding
occurred in Louisiana, Mississippi, and
Alabama. Experts estimate that Katrina
caused more than $100 billion in damage.
Roof systems from the Superdome in
New Orleans to hospitals on the Alabama
gulf coast were damaged from the exposure
to high winds from the storm. Building
owners in many sectors employed the use
of FMG 1-52 testing to determine if their
roof systems would still perform adequately
during high-wind events.
A hospital owner in Alabama hired an
engineering firm to perform testing on all of
the hospital roofs and the adjoining building
roofs. The roof targeted in this Case Study
was 25-30 years old. After discussions with
several professionals regarding the efficacy
of the uplift tests, the testing firm decided
to proceed with the testing with the knowledge
that the roof system was not designed
and installed to FMG requirements. Tests in
conformance with FMG 1-52 were conducted
at five locations on the approximately
30,000-square-foot roof.
Findings and Testing Applicability
Although the intent was to perform the
tests in conformance with FMG 1-90 rating,
all five tests failed at pressures between
one-fourth and one-half of the applicable
test pressures. Test cuts were made at all
test locations. At each location, the test
cut revealed that the pitch built-up roof
assembly was attached to the lightweight
insulating concrete with minimal fasteners
or with no fasteners at all. The aged roof
system withstood the force of a major hurricane
and exhibited few signs of distress.
Roof system performance under FMG 1-52
testing in this instance did not correlate
with the roof system’s performance during
a major wind storm.
Case Study 3
Building Type: Manufacturing Facility
Location: Houston, Texas
Roof Age: New construction
Roof Deck: 22-gauge metal deck
Roof Construction: 2½ in. polyisocyanurate
insulation
½ in. high-density
g ypsum cover board
60-mil PVC membrane,
fully adhered
Roof Height: Varied from 22 to 46 ft.
Roof Uplift Pressures (Test):
Passing uplift test
pressures provided by
FMG for each roof
location
Building 1 Building 2 Building 3
Field 56 psf 56 psf 56 psf
Perimeter 80 psf 80 psf 74 psf
Corner 120 psf 120 psf 110 psf
The manufacturing facility was owned
by an international firm that was insured
by FMG. During the design process, the
general contractor and subcontractors were
informed that FMG would provide design
comments and follow-up site visits during
construction. Testing in conformance
with FMG 1-52 was included in the roofing
specification, and knowledge of the testing
was transmitted to the general contractor
and subcontractor at several preconstruction
meetings. The roofing subcontractor
acknowledged the testing criteria, even stating
that he had installed roofs where the
FMG testing protocols had been used and
that he had not had problems with those
roof applications.
Findings and Test Applicability
Upon completion of the field testing,
approximately one-third of the test locations
failed. Test cuts were taken at these
locations to determine the mode of failure.
In most instances, it appeared that bonding
adhesive was installed properly. At several
locations, dry-lay sheets were discovered.
From these test cuts it was determined that
the bonding adhesive had been applied in
the proper amounts; however, they had not
been installed in the window of time while
the adhesive was still “sticky.” At other
locations, the adhesive appeared to have
not been installed in a sufficient amount to
provide for proper adhesion. In these areas,
the PVC sheet easily peeled back from the
cover board beyond the test cut area.
The engineering firm, with assistance
from the manufacturer, conducted additional
test cuts to determine the extent
of the problem. After additional mapping
of each roof, it was determined that the
problem areas could be isolated and effectively
repaired. The manufacturer provided
a fastener layout that required the roofing
subcontractor to install fasteners well
beyond the problem areas to ensure that
the problem areas did not experience tributary
problems. After the installation of the
additional fasteners, an overlay of new PVC
sheet was installed, totally adhered to the
fasteners and existing PVC material.
In this case, the performance criteria
and the metrics required to determine performance
criteria were clearly stated, and
a system capable of meeting the criteria
was specified. Through field uplift testing,
construction deficiencies associated with
failure of the roof system below threshold
amounts were discovered. However, through
study of the test results and a rational
approach to evaluating the roof system,
deficient areas were isolated and reasonable
remediation was performed. Without field
uplift testing, construction deficiencies may
not have been discovered until a major wind
event occurred, and a reasonable approach
to remediation of the newly installed roof
system likely would not have been achieved.
Case Study 4
Building Type: Medical
Location: Houston
Roof Age: New construction
Roof Deck: Concrete, 22-ga. metal
deck
Roof Construction: Multi layers of polyiso
insulation
½ in. Dens Deck, waterresistant,
gypsum
coverboard
60-mil TPO fully adhered
roof system
Roof Height: Varies
Passing Uplift Test Pressures:
Field 56.25
Perimeter 93.75
Corner 140.63
3 2 n d RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 1 6 – 2 1 , 2 0 1 7 A b e n d r o t h a n d Mc E lv o g u e • 1 9 7
Passing Uplift Test Pressures (ASTM
E907-96 Test):
Field 90
Perimeter 150
Corner 225
Field uplift tests were performed on the
above-noted hospital in Houston, Texas.
Four original locations were to be tested;
however, after initial failures, two additional
test locations (two perimeter locations:
Test Specimens 4 and 6) were performed, for
a total of six test locations.
Initially, the tests were performed in
accordance with ASTM E907-96. Field test
pressures, determined by ASCE 7, were
provided by the design team. After two of
the initial four tests failed, the prescribed
deflection limit of 1 in., the consultant
calculated test pressures as required by
FMG 1-52/1-28. Although the resulting test
pressures were less than that provided by
the design team, one of the two additional
tests performed failed performance requirements
under FMG 1-52. Therefore, the roof
assemblies did not meet required performance
specified by the design team or the
alternative FMG 1-52 standard. See results
in Table 4.
Findings and Test Applicability
Following testing, roof cuts and selective
roofing demolition were performed at failed
test locations and other roof perimeter and
corner conditions. Observations of the roof
cuts and at demolished conditions indicated
inconsistent and inaccurate spacing
between roofing system adhesive ribbons.
The spacing of the ribbon adhesive was
generally greater than what is required and
not in accordance with the roofing manufacturer’s
instructions for the perimeter and
corner zones of the specified roof assembly.
As a result of the insufficient adhesion of
the roofing components, the roofing assembly
was generally unable to meet the ASTM
907 or FMG 1-52 roof uplift performance
criteria.
Based on the consistent correlation
between the failed test results and locations
where construction deficiencies were
observed, field uplift testing served to provide
an accurate measure of roof construction
compliance.
Case Study 5
Building Type: Medical professional
building
Location: Houston, Texas
Roof Age: 1 year
Roof Deck: Concrete over metal deck
Roof Construction: Multiple layers of
polyiso insulation
½ in. water-resistant
g ypsum coverboard
Two-ply modified
bitumen roof system
Roof Height: 115 feet
Passing Uplift Test Pressures
(Design & Test):
Field 90
Perimeter 105
Corner 135
According to the National Hurricane
Center’s January 23, 2009, report,
Hurricane Ike made landfall in Texas on
September 13 with recorded sustained
winds of 95 mph. The huge storm knocked
out power to the Houston-Galveston area for
over three weeks, causing billions of dollars
in damage. The hospitals in the region were
subjected to the force of this storm, and
many roofs were damaged or destroyed as
the result of the wind uplift forces associated
with it.
On one of the newer hospital buildings,
a roof system that had been in service
for less than a year failed in several large
areas. A decision was made to replace the
roof while keeping the building in service.
A contractor was chosen, and a new twoply
modified bitumen roof was installed.
After installation of the roof system, loose
areas (bulged and debonded) were observed
throughout the roof areas. After contacting
the general contractor, roofing subcontractor,
and the manufacturer, eight FMG 1-52
negative-pressure field uplift tests were
performed. The tests failed at very low pressures
(30% or less of design/test pressure).
Test cuts were taken at all eight test locations,
and delamination was observed at
either the cover board or polyisocyanurate
insulation facers.
After the test report was issued, the
roofing contractor and manufacturer asked
for permission to conduct bonded-pull testing.
The owner voiced objection, but agreed
to the testing procedure. A testing agency
was chosen and the tests were conducted.
Table 5 is representative of their findings.
The bonded uplift tests did not correlate
to the chamber testing conducted
several weeks earlier. After further review
of the test results, it was determined that
the testing agency did not conduct the
test using the correct pressures. Rather
than using a test pressure for a 2- x 2-ft.
sample, they instead used pressures associated
with a 1-sq.-ft. area. Therefore, the
resulting test method subjected the test
specimens to approximately one-fourth of
the required uplift force. The test results
were not valid.
Another testing agency was commissioned
to perform the bonded pull testing.
In the second instance, the results of the
bonded pull tests closely mirrored those of
the dome tests. Presented with the results
of the second, valid, bonded pull tests, the
roofing subcontractor and manufacturer,
with the roof consultant, prepared a plan to
add securement to the roof system.
Test Applicability
After missteps with the initial bonded
pull testing, subsequent bonded pull testing
correlated with the initial negative pressure
uplift testing and deficiencies observed in
the roof system. Therefore, both test methods
provided reliable confirmation that the
roof assemblies did not posses the specified
uplift resistance.
1 9 8 • A b e n d r o t h a n d Mc E lv o g u e 3 2 n d RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 1 6 – 2 1 , 2 0 1 7
Table 4 – Test results summary.
Test Number Test Deflection Comments
Pressure (inches)
(psf)
Test 1 (Field) 90 0.1 Passed
Test 2 (Perimeter) 150 1.03 Failed at test pressure of 75 psf
Test 3 (Field) 90 0.08 Passed
Test 4 (Perimeter) 150 1.15 Failed at test pressure of 60 psf
Test 5 (Corner) 225 1.56 Failed at test pressure of 105 psf
Test 6 (Perimeter) 150 .09 Passed
* = Exceeds allowable deflection
CONCLUSIONS
As with any testing, field uplift tests
must be conducted in a manner that follows
the parameters set forth in the specifications
or test protocol. Common sense
must be used in the selection of the test
areas, performance of the testing, and in
the interpretation and use of the results.
Specifications for new roof systems should
include the type of testing, test pressures,
locations and numbers of tests, and any
other relevant information so that the contractor
can develop a comprehensive plan
for installation of a successful roofing system.
Roof monitoring during construction is
an important element of a successful roofing
installation. However, despite concerns
with field uplift testing, uplift testing is a
viable tool to help determine a roof system’s
ability to withstand potential wind events.
As noted in the sections above, the
use of field uplift testing to determine the
acceptability of an older existing roof system
where clear performance criteria has
not been established and agreed to by all
parties should not be performed unless a
sound methodology such as comparative
testing (determining if roof performance
is consistent across all areas of the roof)
is established. For applicable existing roof
system projects, bonded pull tests should
provide comparable results to negative pressure
testing, provided sufficient sampling is
performed. The selection of the test method
and target/passing test pressures for the
roof system should be decided based on all
of the pertinent criteria, including applicability
of the test with the type of roof system
constructed, potential damage to the roof,
and number of tests that should be performed.
Finally, unless full-time monitoring
of roof systems can be performed, roof uplift
testing should be considered a useful tool
in new roof construction quality assurance
programs and the evaluation of recently
completed roofing projects.
3 2 n d RC I I n t e r n a t i o n a l C o n v e n t i o n a n d T r a d e S h ow • Ma rc h 1 6 – 2 1 , 2 0 1 7 A b e n d r o t h a n d Mc E lv o g u e • 1 9 9
Test Number Temperature °F Lbs. of Pressure Pass/Fail
1 (Perimeter) 75 134 Pass
2 (Perimeter) 74 105 Pass
3 (Field) 80.8 90 Pass
4 (Field) 54.8 90 Pass
5 (Field) 53.9 90 Pass
6 (Field) 60 90 Pass
7 (Field) 62.5 90 Pass
Table 5 – Bonded uplift test results summary.